4 mincritical
Red Lion Controls N-Tron 700 Series (CVE-2026-32645, CVE-2026-39460, CVE-2026-28745 +4 more)
Seven vulnerabilities in Red Lion Controls N-Tron 700 Series switches enable unauthenticated admin access, credential theft, malicious firmware pushes, and DoS via reboot loop on firmware <=3.11.0. Unauthenticated SNMP access permits config file exfiltration containing plaintext or weakly encrypted credentials, enabling full admin takeover. A specific web URL triggers repeated reboots for denial of service. Firmware and bootloader updates require no authentication, allowing malicious image injection.
Sens:■ ImmediateConf:highAnalyzed:2026-11-05Z.ai
Authors: CISA, Idaho National Laboratory
Source:CISA
Detection / HunterZ.ai
Immediate Actions
- Upgrade all N-Tron 700 Series switches to firmware 3.11.1 or later.
- Disable web GUI access on all affected switches immediately.
- Configure or disable SNMP communities on all affected switches.
- Restrict network access to switch management interfaces via firewall rules.
Key Takeaways
- Default factory admin credentials persist even after configuring new administrator accounts (CVE-2026-32645).
- SNMP allows unauthenticated administrative actions including config retrieval and firmware changes (CVE-2026-33367).
- Credentials stored in plaintext or with weak encryption inside configuration files (CVE-2026-39460, CVE-2026-28745).
- Specific web URL triggers switch reboot; automatable with curl for persistent DoS (CVE-2026-39453).
- Physical access allows factory boot bypass using default credentials (CVE-2026-33272).
Attack Chain
- Initial Access: Attacker uses persistent default factory credentials or unauthenticated SNMP to access switch
- Credential Access: Configuration file exfiltrated via SNMP-triggered TFTP contains plaintext or weakly encrypted passwords
- Persistence: Attacker modifies user accounts or pushes malicious firmware/bootloader without authentication
- Impact: Attacker navigates to specific URL causing repeated switch reboots for denial of service
Affected Systems
- Red Lion N-Tron 700 Series firmware <=3.11.0
- Red Lion N-Tron 700 Series bootloader <=2.0.6.1
Vulnerabilities (CVEs)
| CVE | Product | Severity | Description |
|---|---|---|---|
| CVE-2026-32645 | Red Lion Controls N-Tron 700 Series | Critical | Default factory admin credentials persist after configuring other admin accounts. |
| CVE-2026-39460 | Red Lion Controls N-Tron 700 Series | Critical | Credentials stored in plaintext in config file, retrievable via unauthenticated SNMP-triggered TFTP. |
| CVE-2026-28745 | Red Lion Controls N-Tron 700 Series | Critical | Credentials stored with weak encryption in config file, enabling credential recovery. |
| CVE-2026-33367 | Red Lion Controls N-Tron 700 Series | Critical | SNMP enables unauthenticated admin actions: config retrieval, account modification, firmware changes. |
| CVE-2026-29797 | Red Lion Controls N-Tron 700 Series | High | No authentication required for firmware or bootloader updates via SNMP/TFTP. |
| CVE-2026-39453 | Red Lion Controls N-Tron 700 Series | High | Specific web URL causes switch reboot; automatable for persistent DoS. |
| CVE-2026-33272 | Red Lion Controls N-Tron 700 Series | Medium | Physical access enables factory boot bypass using default credentials to gain admin access. |
Detection Engineering Assessment
Hunting Hypotheses
| Hypothesis | Telemetry | Stage | FP Risk |
|---|---|---|---|
| Unauthenticated SNMP requests to N-Tron switches retrieving config files or modifying accounts (T1078.001, T1552.001) | SNMP traffic to switch management IPs | Credential Access | Medium — legitimate SNMP monitoring may generate similar traffic |
| Repeated HTTP requests to a specific URL on N-Tron switch causing reboots (T1499, T1190) | HTTP access logs or network flow to switch web interface | Impact | Low — repeated requests to same URL from single source unusual |
| TFTP firmware transfer initiated via SNMP to N-Tron switch without prior authentication (T1601) | TFTP transfer logs and SNMP set requests | Persistence | Medium — scheduled firmware updates may use same pattern |
Required Log Sources
- Network flow logs
- SNMP traffic captures
- TFTP transfer logs
- Switch management interface logs
- Firewall logs to switch subnets
Control Gaps
- SNMP community strings provide no authentication for admin actions
- Web GUI lacks rate limiting or access controls for reboot URL
- Firmware update process has no integrity verification
- Configuration file encryption is weak or absent
Recommendations
Infrastructure Hardening
- Isolate ICS network segments from business networks using firewalls.
- Block SNMP and TFTP traffic from non-management subnets to switches.
- Require VPN for remote access to control system networks.
- Monitor SNMP and TFTP traffic to N-Tron devices for anomalous patterns.
User Protection
- Change all default credentials on N-Tron switches after firmware upgrade.
- Rotate any credentials previously stored in exported configuration files.
- Restrict physical access to network switches in facilities.
MITRE ATT&CK Mapping
MITRE ATT&CK Mapping10 techniques
Tactic
Initial Access
Tactic
Execution
Tactic
Persistence
Tactic
Defense Impairment
Tactic
Credential Access
Tactic
Impact
Showing defanged values
- cveCVE-2026-28745Credentials stored with weak encryption in config file, enabling credential recovery.
- cveCVE-2026-29797No authentication required for firmware or bootloader updates via SNMP/TFTP.
- cveCVE-2026-32645Default factory admin credentials persist after configuring other admin accounts.
- cveCVE-2026-33272Physical access enables factory boot bypass using default credentials to gain admin access.
- cveCVE-2026-33367SNMP enables unauthenticated admin actions: config retrieval, account modification, firmware changes.
- cveCVE-2026-39453Specific web URL causes switch reboot; automatable for persistent DoS.
- cveCVE-2026-39460Credentials stored in plaintext in config file, retrievable via unauthenticated SNMP-triggered TFTP.