4 mincritical
Grid Protection Alliance openPDC and openHistorian (CVE-2026-104629, CVE-2026-100730, CVE-2026-105281 +3 more)
Six CVEs in Grid Protection Alliance openPDC and openHistorian enable unauthenticated remote code execution, topology disclosure, and network mapping in energy-sector ICS. The deserialization flaw (CVE-2026-100730, CVSS 9.8) allows unauthenticated network attackers to achieve RCE via the service console interface on systems without Windows Authentication. The openPDC Docker image ships with a fixed administrative credential (CVE-2026-105278, CVSS 9.8). Patches exist in openPDC 2.9.482 and openHistorian 2.8.585; Docker images remain unfixed.
Sens:▲ 24h
Detection / HunterZ.ai
Immediate Actions
- Upgrade openPDC to 2.9.482+ and openHistorian to 2.8.585+.
- Bind internal data publisher and STTP interfaces to localhost only.
- Restrict Modbus network access with firewall; block RFC1918 destinations.
- Replace or disable published Docker images in production environments.
Key Takeaways
- Docker images for openPDC have no fix planned; vendor does not recommend production use.
- Windows Authentication mitigates CVE-2026-100730 by requiring authentication to reach vulnerable function.
- CVE-2026-105281 exposes complete device and measurement topology to unauthenticated network attackers.
- openPDC 2.9.477+ and openHistorian 2.8.580+ fix CVE-2026-104629; 2.9.482 and 2.8.585 fix the rest.
- No known public exploitation targeting these vulnerabilities reported to CISA.
Attack Chain
- Initial Access: Unauthenticated attacker accesses network-exposed openPDC or openHistorian service
- Reconnaissance: CVE-2026-105281 retrieves complete device and measurement topology without authentication
- Execution: CVE-2026-100730 deserializes untrusted data triggering remote code execution as service account
- Discovery: CVE-2026-101022 uses Modbus SSRF to probe and map internal network destinations
- Persistence: CVE-2026-104629 exploits unsafe reflection to run arbitrary code via file placement
Affected Systems
- Grid Protection Alliance openPDC <2.9.482
- Grid Protection Alliance openPDC Docker image <2.9.482
- Grid Protection Alliance openHistorian <2.8.585
- Energy sector operational technology systems worldwide
Vulnerabilities (CVEs)
| CVE | Product | Severity | Description |
|---|---|---|---|
| CVE-2026-100730 | Grid Protection Alliance openPDC and openHistorian | Critical | Deserialization of untrusted data enables unauthenticated remote code execution. |
| CVE-2026-105278 | Grid Protection Alliance openPDC Docker image | Critical | Docker image includes fixed admin credential enabling full administrative access. |
| CVE-2026-104629 | Grid Protection Alliance openPDC and openHistorian | High | Unsafe reflection allows authenticated user to execute arbitrary constructor code. |
| CVE-2026-105281 | Grid Protection Alliance openPDC and openHistorian | High | Unauthenticated attacker retrieves complete device and measurement topology. |
| CVE-2026-85479 | Grid Protection Alliance openPDC | Medium | Unauthenticated network attacker exchanges data with STTP data publisher. |
| CVE-2026-101022 | Grid Protection Alliance openPDC | Medium | Modbus connection feature allows SSRF for internal network mapping. |
Detection Engineering Assessment
Hunting Hypotheses
| Hypothesis | Telemetry | Stage | FP Risk |
|---|---|---|---|
| Unauthenticated connections to openPDC data publisher retrieve device and measurement topology (T1590.002). | Network flow to data publisher port | Reconnaissance | Low — only service accounts should connect |
| Modbus connections from openPDC attempt to reach internal RFC1918 addresses (T1046). | Network firewall logs for Modbus traffic | Discovery | Medium — some Modbus traffic is legitimate |
| Authentication to openPDC Docker management interface using default admin credentials (T1078). | Authentication logs for management interface | Initial Access | Low — default credentials should not be used |
Required Log Sources
- Network firewall logs
- Network flow data
- Application server access logs
- DNS logs
- OT/ICS network monitoring
Control Gaps
- Unauthenticated network access to data publisher interfaces
- Modbus SSRF allows probing internal RFC1918 ranges
- Docker image ships with unchanged default credentials
- Upgraded installations retain old insecure configurations
Recommendations
Infrastructure Hardening
- Isolate ICS networks from business networks using firewalls.
- Enforce Windows Authentication on openPDC and openHistorian services.
- Block all internet access to control system devices and services.
- Use VPNs with current updates for any required remote access.
User Protection
- Monitor for unauthenticated connections to data publisher interfaces.
- Restrict network access to energy sector OT systems.
- Verify openPDC and openHistorian interface bindings after upgrades.
MITRE ATT&CK Mapping
MITRE ATT&CK Mapping5 techniques
Tactic
Reconnaissance
Tactic
Initial Access
Tactic
Credential Access
Tactic
Discovery
Showing defanged values
- cveCVE-2026-100730Deserialization of untrusted data enables unauthenticated remote code execution.
- cveCVE-2026-101022Modbus connection feature allows SSRF for internal network mapping.
- cveCVE-2026-104629Unsafe reflection allows authenticated user to execute arbitrary constructor code.
- cveCVE-2026-105278Docker image includes fixed admin credential enabling full administrative access.
- cveCVE-2026-105281Unauthenticated attacker retrieves complete device and measurement topology.
- cveCVE-2026-85479Unauthenticated network attacker exchanges data with STTP data publisher.
Related
- Armatura LLC Armatura One (CVE-2023-46604, CVE-2026-94591, CVE-2026-94592 +2 more)·2
- Digital Watchdog VMAX DVR and NVR Product Lineups (CVE-2026-68953, CVE-2026-66890, CVE-2026-68070 +3 more)·2
- Johnson Controls C-CURE 9000 and Victor application server (Update A) (CVE-2026-21655, CVE-2026-34496, CVE-2026-21653)·2
Stay current